5 - 12
5. PARAMETERS
Class
No.
Symbol
Name and function
Initial
value
Unit
Setting
range
Control
mode
22
*OP4 Function selection 4
Used to select stop processing at forward rotation stroke end (LSP)
reverse rotation stroke end (LSN) off and choose TLC/VLC output.
0 0
How to make a stop when forward
rotation stroke end (LSP)
reverse rotation stroke end (LSN)
is valid. (Refer to Section 5.2.3.)
0: Sudden stop
1: Slow stop
0
0000
Refer to
Name
and
function
column.
P S
23
FFC
Feed forward gain
Set the feed forward gain. When the setting is 100%, the droop pulses
during operation at constant speed are nearly zero. However, sudden
acceleration/deceleration will increase the overshoot. As a guideline,
when the feed forward gain setting is 100%, set 1s or more as the
acceleration/deceleration time constant up to the rated speed.
0
%
0
to
100
P
24
ZSP
Zero speed
Used to set the output range of the zero speed (ZSP).
50
r/min
0
to
10000
P S
25
For manufacturer setting
Don’t change this value by any means.
0
Ex
pan
si
on
par
ame
te
rs
1
26
For manufacturer setting
Don’t change this value by any means.
100
Summary of Contents for GENERAL PURPOSE AC SERVO MR-E- A/AG
Page 1: ...General Purpose AC Servo MODEL MR E A AG INSTRUCTION MANUAL B ...
Page 11: ...A 10 MEMO ...
Page 17: ...6 MEMO ...
Page 31: ...2 4 2 INSTALLATION MEMO ...
Page 85: ...4 6 4 OPERATION MEMO ...
Page 149: ...8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 163: ...10 12 10 TROUBLESHOOTING MEMO ...
Page 307: ...15 62 15 MR E AG SERVO AMPLIFIER COMPATIBLE WITH ANALOG INPUT MEMO ...