2 - 2
2. INSTALLATION
2.2 Installation direction and clearances
CAUTION
The equipment must be installed in the specified direction. Otherwise, a fault may
occur.
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
(1) Installation of one servo amplifier
MODE
CN3
SET
CN1
CN2
CNP2
CNP1
L3
L
2
L1
D
C
P
W
V
U
CH
A
R
G
E
MITSUBISHI
MR-
Control box
Control box
10mm
(0.4 in.)
or more
10mm
(0.4 in.)
or more
40mm
(1.6 in.)
or more
Servo
amplifier
40mm
(1.6 in.)
or more
Wiring clearance
Top
Bottom
(2.8 in.)
70mm
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
MODE
CN3
SET
CN1
CN2
CNP2
CNP1
L3
L
2
L1
D
C
P
W
V
U
CH
A
R
G
E
MITSUBISHI
MR-
MODE
CN3
CN1
CN2
CNP2
CNP1
L3
L
2
L1
D
C
P
W
V
U
CH
A
R
G
E
MITSUBISHI
MR-
SET
Control box
30mm
(1.2 in.)
or more
30mm
(1.2 in.)
or more
10mm
(0.4 in.)
or more
40mm
(1.6 in.)
or more
100mm
(4.0 in.)
or more
Summary of Contents for GENERAL PURPOSE AC SERVO MR-E- A/AG
Page 1: ...General Purpose AC Servo MODEL MR E A AG INSTRUCTION MANUAL B ...
Page 11: ...A 10 MEMO ...
Page 17: ...6 MEMO ...
Page 31: ...2 4 2 INSTALLATION MEMO ...
Page 85: ...4 6 4 OPERATION MEMO ...
Page 149: ...8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 163: ...10 12 10 TROUBLESHOOTING MEMO ...
Page 307: ...15 62 15 MR E AG SERVO AMPLIFIER COMPATIBLE WITH ANALOG INPUT MEMO ...