(2) 6-point frequency jump
(Pr.552)
2 SERIAL number
Check the SERIAL number indicated on the inverter rating plate or package.
• SERIAL number check
Refer to the inverter manual for the location of the rating plate.
The total of six jump ranges can be set using
Pr.31
to
Pr.36
.
When frequency jump ranges overlap, the
lower limit of the lower jump range and the
upper limit of the upper jump range are used.
When a frequency is set to a point within a
jump range, the set frequency is lowered or
increased to the jump range limits, according
to the following frequency input condition.
REMARKS
Setting
Pr.552
= "0" disables frequency jumps.
During acceleration/deceleration, the running frequency within the set
area is valid.
Rating plate example
4
3
Symbol
Year
Month
Control number
SERIAL
The SERIAL consists of one symbol, two characters indicating production
year and month, and six characters indicating control number.
The last digit of the production year is indicated as the Year, and the Month
is indicated by 1 to 9, X (October), Y (November), or Z (December.)
Pr.36
Pr.31
0
Pr.32
Pr.34
Pr.33
Pr.35
Set frequency after frequency jump
Input set frequency
Jump range
Jump range
Pr.552
Pr.552
Frequency
input
condition
Set frequency after
frequency jump
When
accelerating
The setting frequency is decreased to
the lower limit of the jump range.
When
decelerating
The setting frequency is increased to
the upper limit of the jump range.