197
Communication operation and setting
[Fault data]
Refer to
page
for details of fault description
[Run command]
∗1
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 180 to Pr. 182 (input terminal function selection) (page 114)
.
∗2
When
Pr. 551
= "2" (PU mode control source is PU connector), only forward rotation and reverse rotation can be used.
[Inverter status monitor]
∗
The signal within parentheses is the initial setting. The description changes depending on the
Pr. 190, Pr. 192 and Pr. 197 (output terminal function selection)
.
....Specifications differ according to the date assembled.
to check the SERIAL number.
Item
Instruction
Code
Bit
Length
Description
Example
Run
command
HFA
8 bits
b0: AU (terminal 4 input selection)
b1: forward rotation command
b2: reverse rotation command
b3: RL (low-speed operation
command)
∗1∗2
b4: RM (middle-speed operation
command)
b5: RH (high-speed operation
command)
∗1∗2
b6: RT (second function selection)
b7: MRS (output stop)
Run
command
(expansion)
HF9
16 bits
b0: AU (terminal 4 input selection)
b1: forward rotation command
b2: reverse rotation command
b3: RL
(low-speed operation
command)
∗1∗2
b4: RM (middle-speed operation
command)
b5: RH (high-speed operation
command)
∗1∗2
b6: RT (second function selection)
b7: MRS (output stop)
b8 to b15: —
Item
Instruction
Code
Bit
Length
Description
Example
Inverter
status
monitor
H7A
8 bits
b0: RUN (inverter running)
∗
b1: Forward rotation
b2: Reverse rotation
b3: SU (up-to-frequency)
b4: OL (overload)
b5: —
b6: FU (frequency detection
)
b7: ABC (fault)
∗
Inverter
status
monitor
(expansion)
H79
16 bits
b0: RUN (inverter running)
∗
b1: During forward rotation
b2: During reverse rotation
b3: SU (up-to-frequency)
b4: OL (overload)
b5: —
b6: FU (frequency detection
)
b7: ABC (fault
) ∗
b8: —
b9: SO (safety monitor output
) ∗
b10 to b14: —
b15: Fault occurrence
For read data H3010
(Previous fault ...... THT)
(Latest fault...OC1)
0
1
0
1 0 0 0 0
0
1
0
0
0
0
0
0
b15
b8b7
b0
Latest fault
(H10)
Previous fault
(H30)
Fault record display example (instruction code H74)
Data
Definition
H00
No fault
present
H10
E.OC1
H11
E.OC2
H12
E.OC3
H20
E.OV1
H21
E.OV2
H22
E.OV3
H30
E.THT
H31
E.THM
H40
E.FIN
H52
E.ILF
H60
E.OLT
H70
E.BE
H80
E.GF
H81
E.LF
H90
E.OHT
H91
E.PTC
Data
Definition
HB0
E.PE
HB1
E.PUE
HB2
E.RET
HC0
E.CPU
HC4
E.CDO
HC5
E.IOH
HC7
E.AIE
HC9
E.SAF
HF5
E.5
Data
Definition
0
0
0
0
0
0
1
0
b7
b0
[Example 1] H02... Forward rotation
[Example 2] H00... Stop
0
0
0
0
0
0
0
0
b7
b0
0
0
0
0
0
0
1
0
b0
[Example 1] H0002... Forward rotation
0
0
0
0
0
0
0
0
b15
0
0
1
0
0
0
0
0
b0
0
0
0
0
0
0
0
0
b15
[Example 2] H0020... Low speed operation
(When
Pr. 182 RH terminal function selection
is set to "0")
0
0
0
0
0
0
1
0
b7
b0
[Example 1] H02... During forward rotation
[Example 2] H80... Stop at fault occurrence
1
0
0
0
0
0
0
0
b7
b0
0
0
0
0
0
0
1
0
b0
0
0
0
0
0
0
0
0
b15
[Example 1] H0002... During forward rotation
1
0
0
0
0
0
0
0
b0
1
0
0
0
0
0
0
0
b15
[Example 2] H8080... Stop at fault occurrence
Summary of Contents for FR-D710W-0.1K
Page 45: ...36 MEMO ...
Page 61: ...52 MEMO ...
Page 254: ...252 MEMO ...
Page 296: ...294 MEMO ...
Page 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Page 312: ...4 4 BCN C22005 689 MEMO ...