![Mitsubishi Electric FR-D710W-0.1K Instruction Manual Download Page 306](http://html.mh-extra.com/html/mitsubishi-electric/fr-d710w-0-1k/fr-d710w-0-1k_instruction-manual_239791306.webp)
2/4
BCN-C22005-652
(1) 3-point frequency jump
(Pr.31 to Pr.36)
Up to three areas may be set, with the
jump frequencies set to either the top or
bottom point of each area.
The value set to 1A, 2A or 3A is a jump
point, and operation in the jump zone is
performed at these frequencies.
Example 1
To fix the frequency to 30Hz in the range of 30Hz to
35Hz, set 35Hz in
Pr.34
and 30Hz in
Pr.33
.
Example 2
To jump the frequency to 35Hz in the range of 30Hz to
35Hz, set 35Hz in
Pr.33
and 30Hz in
Pr.34
.
REMARKS
During acceleration/deceleration, the running frequency within the set
area is valid.
If the setting ranges of individual groups (1A and 1B, 2A and 2B, 3A
and 3B) overlap, Er1 (write disable error) will occur.
Pr. 31
Pr. 32
Pr. 33
Pr. 34
Pr. 35
Pr. 36
Frequency jump
Set frequency (Hz)
Pr. 34
: 35Hz
Pr. 33
: 30Hz
Pr. 33
: 35Hz
Pr. 34
: 30Hz