![Mitsubishi Electric FR-D710W-0.1K Instruction Manual Download Page 305](http://html.mh-extra.com/html/mitsubishi-electric/fr-d710w-0-1k/fr-d710w-0-1k_instruction-manual_239791305.webp)
1/4
BCN-C22005-652
FR-D
700
Series
Instruction Manual Supplement
For the FR-D700 series manufactured in March 2014 or later, the
following specifications are added. Check the serial number
printed on the rating plate or on package of the inverter.
(For how to find the SERIAL number, refer to
page 3
.)
1 6-point frequency jump
(Pr.552)
The above parameters can be set when
Pr.160 User group read selection
= "0".
(
Refer to
Chapter 4 of the Instruction Manual (Applied)
)
When it is desired to avoid resonance attributable to the natural frequency of a
mechanical system, these parameters allow resonant frequencies to be jumped.
Pr.
Name
Initial
value
Setting
range
Description
31
Frequency jump 1A
9999
0 to 400Hz,
9999
1A to 1B, 2A to 2B, 3A to 3B are
frequency jumps (3-point jump)
9999: Function invalid
32
Frequency jump 1B
9999
0 to 400Hz,
9999
33
Frequency jump 2A
9999
0 to 400Hz,
9999
34
Frequency jump 2B
9999
0 to 400Hz,
9999
35
Frequency jump 3A
9999
0 to 400Hz,
9999
36
Frequency jump 3B
9999
0 to 400Hz,
9999
552
Frequency jump
range
9999
0 to 30Hz,
9999
Jump range for the six frequency jumps.
9999: 3-point jump