Special operation and frequency control
(5) PID automatic switchover control
(Pr. 127)
The system can be started up without PID control only at a start.
When the frequency is set to
Pr. 127 PID control automatic switchover frequency
within the range 0 to 400Hz, the inverter
starts up without PID control from a start until output frequency is reached to the set frequency of
Pr. 127
, and then it shifts
to PID control. Once the system has entered PID control operation, it continues PID control even if the output frequency
falls to or below
Pr.127
.
(6) PID output suspension function (SLEEP function) (SLEEP signal,
Pr. 575 to Pr. 577
)
The inverter stops operation if the output frequency after PID operation remains at less than the
Pr. 576 Output interruption
detection level
setting for longer than the time set in
Pr. 575 Output interruption detection time
. This function can reduce
energy consumption in the low-efficiency, low-speed range.
When the deviation (= set value - measured value) reaches the PID output shutoff cancel level (
Pr. 577
setting -1000%)
while the PID output interruption function is ON, the PID output interruption function is canceled and PID control operation
is resumed automatically.
While the PID output interruption function is ON, the PID output interruption signal (SLEEP) is output. At this time, the
inverter running signal (RUN) is OFF, and the PID control operating signal (PID) is ON.
For the terminal used for the SLEEP signal output, assign the function by setting "70" (positive logic) or "170" (negative
logic) in
Pr. 190, Pr. 192 or Pr. 197 (output terminal function selection)
.
(7) PID monitor function
The PID control set point, measured value and deviation value can be displayed on the operation panel and output from
terminal FM.
Integral value indicating a negative % can be displayed on the deviation monitor. 0% is displayed as 1000. (The deviation
monitor cannot be output from the terminal FM.)
For each monitor, set the following value in
Pr. 52 DU/PU main display data selection
and
Pr. 54 FM terminal function selection
.
Setting
Monitor Description
Minimum
Increments
Terminal FM
Full Scale
Remarks
52
PID set point
0.1%
100%
—
53
PID measured value
0.1%
100%
54
PID deviation
0.1%
—
Value cannot be set to
Pr. 54
.
Displays 1000 when the PID deviation is 0%.
Output frequency
Pr. 127
STF
Time
PID
Without
PID control
PID control
Output frequency
Deviation
Reverse action (
Pr.128
10)
Pr.576
Pr.577
- 1000%
RUN
Time
ON
OFF
SLEEP
Less than
Pr. 575
Pr. 575
or more
SLEEP period
PID
Cancel
level