![Mitsubishi Electric FR-D710W-0.1K Instruction Manual Download Page 196](http://html.mh-extra.com/html/mitsubishi-electric/fr-d710w-0-1k/fr-d710w-0-1k_instruction-manual_239791196.webp)
194
Communication operation and setting
(7) Setting items and set data
After completion of parameter settings, set the instruction codes and data then start communication from the computer to
allow various types of operation control and monitoring.
Item
Read/
Write
Instruction
Code
Data Definition
Number of
Data Digits
(Format)
Operation mode
Read
H7B
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
H0002: PU operation mode, External/PU combined operation mode 1 and
2, PUJOG operation mode
4 digits
(B, E/D)
Write
HFB
H0000: Network operation mode
H0001: External operation mode
H0002: PU operation mode (
Pr. 79
= "6")
4 digits
(A, C/D)
Mo
n
ito
r
Output
frequency
/speed
Read
H6F
H0000 to HFFFF: Output frequency in 0.01Hz increments
Speed increments 1/0.001 (when
Pr. 37
= 0.01 to 9998)
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the
increments change to 0.001 and the data format is E2.
When "100" is set in
Pr. 52
, the monitor value is different depending on
whether the inverter is at a stop or running.
4 digits
(B, E/D),
6 digits
(B, E2/D)
Output
current
Read
H70
H0000 to HFFFF: Output current (hexadecimal) in 0.01A increments
4 digits
(B, E/D)
Output
voltage
Read
H71
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1V increments
4 digits
(B, E/D)
Special
monitor
Read
H72
H0000 to HFFFF: Monitor data selected in instruction code HF3
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the
data format is E2.
4 digits
(B, E/D),
6 digits
(B, E2/D)
Special
monitor
Selection No.
Read
H73
H01 to H40: Monitor selection data
Refer to the special monitor No. table
(page 196)
2 digits
(B, E1/D)
Write
HF3
2 digits
(A1, C/D)
Fault records
Read
H74 to H77
H0000 to HFFFF: Two latest fault records
Refer to the alarm data table
(page 197)
4 digits
(B, E/D)
Run command
(extended)
Write
HF9
Control input commands such as forward rotation signal (STF) and reverse
rotation signal (STR). (For details,
refer to page 197
4 digits
(A, C/D)
Run command
Write
HFA
2 digits
(A1, C/D)
Inverter status
monitor (extended)
Read
H79
Monitor the states of the output signals such as forward rotation, reverse
rotation and inverter running (RUN). (For details,
refer to page 197
4 digits
(B, E/D)
Inverter status
monitor
Read
H7A
2 digits
(B, E1/D)
Set frequency
(RAM)
Read
H6D
Read set frequency/speed from RAM or EEPROM.
H0000 to HFFFF: Set frequency in 0.01Hz increments
Speed increments 1/0.001 (when
Pr. 37
= 0.01 to 9998)
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the
increments change to 0.001 and the data format is E2.
4 digits
(B, E/D),
6 digits
(B, E2/D)
Set frequency
(EEPROM)
H6E
Set frequency
(RAM)
Write
HED
Write set frequency/speed to RAM or EEPROM.
H0000 to H9C40 (0 to 400.00Hz): Frequency increments 0.01Hz
Speed increments 1/0.001 (when
Pr. 37
= 0.01 to 9998)
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the
increments change to 0.001 and the data format is A2.
To change the set frequency consecutively, write data to the inverter
RAM. (instruction code: HED)
4 digits
(A, C/D),
6 digits
(A2, C/D)
Set frequency
(RAM, EEPROM)
HEE
Refer to
page 188
for data format (A, A1, A2, A3, B, C, C1, D, E, E1, E2, E3)
b15
b8b7
b0
Latest fault
First fault in past
Second fault in past
Third fault in past
Fourth fault in past
Fifth fault in past
Sixth fault in past
Seventh fault in past
H74
H75
H76
H77
Summary of Contents for FR-D710W-0.1K
Page 45: ...36 MEMO ...
Page 61: ...52 MEMO ...
Page 254: ...252 MEMO ...
Page 296: ...294 MEMO ...
Page 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Page 312: ...4 4 BCN C22005 689 MEMO ...