Communication operation and setting
Parameter
Faults history
Fault code list
Parameter
Register
Parameter Name
Read/
Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list
(page
for the parameter names.
Read/write
The parameter 41000 is the register
number.
C2(902)
41902
Terminal 2 frequency setting
bias frequency
Read/write
C3(902)
42092
Terminal 2 frequency setting bias
(Analog value)
Read/write The analog value (%) set to
C3 (902)
is read.
43902
Terminal 2 frequency setting bias
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
125(903)
41903
Terminal 2 frequency setting gain
frequency
Read/write
C4(903)
42093
Terminal 2 frequency setting gain
(Analog value)
Read/write The analog value (%) set to
C4 (903)
is read.
43903
Terminal 2 frequency setting gain
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
C5(904)
41904
Terminal 4 frequency setting bias
frequency
Read/write
C6(904)
42094
Terminal 4 frequency setting bias
(Analog value)
Read/write The analog value (%) set to
C6 (904)
is read.
43904
Terminal 4 frequency setting bias
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905)
41905
Terminal 4 frequency setting
gain frequency
Read/write
C7(905)
42095
Terminal 4 frequency setting gain
(Analog value)
Read/write The analog value (%) set to
C7 (905)
is read.
43905
Terminal 4 frequency setting gain
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C22(922)
41922
Frequency setting voltage bias
frequency (built-in
potentiometer)
Read/write
C23(922)
42112
Frequency setting voltage bias
(built-in potentiometer)
Read/write The analog value (%) set to
C23 (922)
is read.
C24(923)
41923
Frequency setting voltage gain
frequency (built-in
potentiometer)
Read/write
C25(923)
42113
Frequency setting voltage gain
(built-in potentiometer)
Read/write The analog value (%) set to
C25(923)
is read.
Register
Definition
Read/write
Remarks
40501
Fault history 1
Read/write
Being 2 bytes in length, the data is stored as
"H00
".
Refer to the lowest 1 byte for the error code.
Performing write using the register 40501 batch-
clears the faults history.
Set any value as data.
40502
Fault history 2
Read
40503
Fault history 3
Read
40504
Fault history 4
Read
40505
Fault history 5
Read
40506
Fault history 6
Read
40507
Fault history 7
Read
40508
Fault history 8
Read
Data
Definition
H00
No fault
present
H10
E.OC1
H11
E.OC2
H12
E.OC3
H20
E.OV1
H21
E.OV2
H22
E.OV3
H30
E.THT
H31
E.THM
H40
E.FIN
H52
E.ILF
H60
E.OLT
H70
E.BE
H80
E.GF
H81
E.LF
H90
E.OHT
H91
E.PTC
Data
Definition
HB0
E.PE
HB1
E.PUE
HB2
E.RET
HC0
E.CPU
HC4
E.CDO
HC5
E.IOH
HC7
E.AIE
HC9
E.SAF
HF5
E.5
Data
Definition
*
Refer to page 255
for details of fault description.