![Mitsubishi Electric FR-D710W-0.1K Instruction Manual Download Page 223](http://html.mh-extra.com/html/mitsubishi-electric/fr-d710w-0-1k/fr-d710w-0-1k_instruction-manual_239791223.webp)
221
Special operation and frequency control
(2) Dancer control overview
Performs dancer control by setting 40 to 43 in
Pr. 128 PID action selection.
The main speed command is the speed command of
each operation mode (External, PU, Network). Performs PID control by the position detection signal of the dancer roller, then
the result is added to the main speed command. For acceleration/deceleration of the main speed, set the acceleration time in
Pr. 44 Second acceleration/deceleration time/Pr. 45 Second deceleration time
.
* Set 0s normally to
Pr. 7 Acceleration time
and
Pr.8 Deceleration time
. When the
Pr. 7 and Pr. 8
setting is large, response of dancer control during acceleration/
deceleration is slow.
(3) Connection diagram
Sink logic
Pr. 128 =
41
Pr. 182 =
14
Pr. 190 =
15
∗1
The main speed command differs according to each operation mode (External, PU, Network)
∗2
The used output signal terminal changes depending on the
Pr. 190, Pr. 192, Pr. 197 (output terminal selection)
setting.
∗3
The used input signal terminal changes depending on the
Pr. 178 to Pr. 182 (input terminal selection)
setting.
∗4
The AU signal need not be input.
STF
PID adding value
Main speed
ON
Output frequency
Time
Output frequency
Power supply
MCCB
Inverter
Forward rotation
Reverse rotation
PID control selection
Main speed command
setting potentiometer
*1
R/L1
S/L2
T/L3
STF
STR
RH(X14)
*3
SD
10
2
5
4
*4
U
V
W
*2
(FUP)RUN
SE
Motor
IM
Upper limit
Output signal common
Feedback value of
dancer roll position
Summary of Contents for FR-D710W-0.1K