Selection and protection of a motor
(1) Before performing offline auto tuning
Check the following before performing offline auto tuning.
Make sure General-purpose magnetic flux vector control (
Pr. 80
) is selected. (Tuning can be performed even under V/F
control selected by turning ON X18.)
A motor should be connected. Note that the motor should be at a stop at a tuning start.
The motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity should be
0.1kW or higher)
A high-slip motor, high-speed motor and special motor cannot be tuned. (The maximum frequency is 120Hz.)
As the motor may run slightly, fix the motor securely with a mechanical brake or make sure that there will be no problem
in safety if the motor runs (caution is required especially in elevator). Note that tuning performance is unaffected even if
the motor runs slightly.
Offline auto tuning will not be performed properly if it is performed with a reactor or surge voltage suppression filter (FR-
ASF-H/FR-BMF-H) connected between the inverter and motor. Remove it before start tuning.
(2) Setting
1) Select General-purpose magnetic flux vector control (
2) Set "11" in
Pr. 96 Auto tuning setting/status
.
Tuning motor constants (R1) only without running the motor. (It takes approximately 9s until tuning is completed.)
3) Set the rated motor current (initial value is rated inverter current) in
Pr. 9
Electronic thermal O/L relay
. (
4) Set the rated voltage of motor (initial value is 200V/400V) in
Pr. 83 Rated motor voltage
and rated motor frequency (initial
value is 60Hz) in
Pr. 84 Rated motor frequency
.
(For a Japanese standard motor, etc. which has both 50Hz and 60Hz rated values, use it with an initial value (200V/60Hz
or 400V/60Hz).
5) Set
Pr. 71 Applied motor
according to the motor used.
Motor
Pr. 71
Setting
Mitsubishi standard motor
Mitsubishi high efficiency motor
SF-JR
3
SF-JR 4P 1.5kW or lower
23
SF-HR
43
Others
3
Mitsubishi constant-torque motor
SF-JRCA 4P
13
SF-HRCA
53
Others (SF-JRC, etc.)
13
Other standard motor
—
3
Other constant-torque motor
—
13