![Mitsubishi Electric FR-D710W-0.1K Instruction Manual Download Page 203](http://html.mh-extra.com/html/mitsubishi-electric/fr-d710w-0-1k/fr-d710w-0-1k_instruction-manual_239791203.webp)
201
Communication operation and setting
(3) Message format
Data check time
1)
Query
The master sends a message to the slave (= inverter) at the specified address.
2)
Normal Response
After receiving the query from the master, the slave executes the requested function and returns the corresponding normal
response to the master.
3)
Error Response
If an invalid function code, address or data is received, the slave returns it to the master.
When a response description is returned, the error code indicating that the request from the master cannot be executed is
added.
No response is returned for the hardware-detected error, frame error and CRC check error.
4)
Broadcast
By specifying address 0, the master can send a message to all slaves. All slaves that received the message from the
master execute the requested function. In this communication, the slaves do not return a response to the master.
Item
Check Time
Various monitors, operation command,
frequency setting (RAM)
<20ms
Parameter read/write, frequency setting
(EEPROM)
<50ms
Parameter clear/all clear
<5s
Reset command
No answer
REMARKS
The inverter performs the function independently of the inverter station number setting
(Pr. 117)
during broadcast communication.
Query communication
Broadcast communication
Query message
Query message
Response message
Inverter response time
(Refer to the following table for the data check time)
Data absence time
(3.5 bytes or more)
Inverter (slave)
Inverter (slave)
Programmable controller (master)
Programmable controller (master)
No Response
Summary of Contents for FR-D710W-0.1K
Page 45: ...36 MEMO ...
Page 61: ...52 MEMO ...
Page 254: ...252 MEMO ...
Page 296: ...294 MEMO ...
Page 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Page 312: ...4 4 BCN C22005 689 MEMO ...