VIII
Troubleshooting ]
- 187 -
HWE1410A
GB
6. Solenoid valve and LEV body
Operation procedures
Illustrations
Operation
location
(1) Collect the refrigerant and water and
then carry out the unit from the ceiling
space.
(2) Remove the four fixing screws from the
service panel (right) and then remove
the service panel (right).
(3) Remove the two fixing screws from the
service panel (top right) and then re-
move the service panel (top right).
(4) Disconnect the corresponding valve coil
connectors from the control board and
also remove the coil from the valve.
(For how to remove the coil, follow the
operation procedures of 1.)
(5) Remove the float switch and fixing plate
from the drain pan (to prevent them from
catching fire when the brazing is per-
formed).
Remove the two fixing screws from the
direction of the arrow indicated in the fig-
ure.
(6) Protect the heat insulation material
around the corresponding valve to pre-
vent it from burning.
(7) Debraze the corresponding valve to re-
move it and then replace it.
Below
ceiling
LEV2
LEV1
LEV3
Service panel (top right)
Service panel (right)
Solenoid valve
Float switch
0000002394.book 187 ページ 2016年1月12日 火曜日 午後4時49分
Summary of Contents for CITY MULTI CMB-WP1016V-GA1
Page 1: ......
Page 9: ...HWE1410A GB ...
Page 11: ... 2 HWE1410A GB ...
Page 27: ... I Read Before Servicing 18 HWE1410A GB ...
Page 29: ... 20 HWE1410A GB ...
Page 47: ... 38 HWE1410A GB ...
Page 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Page 57: ... 48 HWE1410A GB ...
Page 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Page 69: ... 60 HWE1410A GB ...
Page 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Page 77: ... 68 HWE1410A GB ...
Page 95: ... 86 HWE1410A GB ...
Page 117: ... VII Test Run Mode 108 HWE1410A GB ...
Page 119: ... 110 HWE1410A GB ...
Page 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Page 209: ... 200 HWE1410A GB ...
Page 294: ......