VIII
Troubleshooting ]
- 146 -
HWE1410A
GB
7107
1. Error
Code
Port setting error
2. Error
definition and error detection method
The port with wrong number is connected to the indoor unit.The model total connected to the port is greater than the specifi-
cation.
3. Cause, check method and remedy
7107
Error source
Cause
Check method and remedy
HBC control-
ler
(1)
Model total of indoor units per each port or per
each port merge is greater than the specification.
Before resetting the port number using
the port number setting switch or the
model using the model (capacity code)
setting switch, turn off the power of the
outdoor unit, the HBC controller and
the indoor unit.
(2)
4 or more indoor units are connected to the same
port.
(3)
When two ports are used, the port with the smaller
number is not connected to the indoor unit.
(4)
The address of the HBC controller is not set to an
address that equals the address of the lowest ad-
dress of the connected indoor unit plus 50.
Model total
Total port number
Single branching
80
0000002394.book 146 ページ 2016年1月12日 火曜日 午後4時49分
Summary of Contents for CITY MULTI CMB-WP1016V-GA1
Page 1: ......
Page 9: ...HWE1410A GB ...
Page 11: ... 2 HWE1410A GB ...
Page 27: ... I Read Before Servicing 18 HWE1410A GB ...
Page 29: ... 20 HWE1410A GB ...
Page 47: ... 38 HWE1410A GB ...
Page 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Page 57: ... 48 HWE1410A GB ...
Page 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Page 69: ... 60 HWE1410A GB ...
Page 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Page 77: ... 68 HWE1410A GB ...
Page 95: ... 86 HWE1410A GB ...
Page 117: ... VII Test Run Mode 108 HWE1410A GB ...
Page 119: ... 110 HWE1410A GB ...
Page 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Page 209: ... 200 HWE1410A GB ...
Page 294: ......