VI
Control ]
- 73 -
HWE1410A
GB
Bypass Control
-5- Bypass Control
Solenoid valves have two types: (SVM1) that bypass the high- and low- pressure sides; LEV (LEV3). They perform the fol-
lowing functions.
(1) Bypass solenoid valve (SVM1) (ON: open)
Plate heat exchanger contro
-6- Plate heat exchanger control
(1) Cooling-only Thermo-ON and Cooling-only test run
When three minutes have passed after the LEV operates with initial opening, the LEV opening is adjusted every 1 minute to
keep the amount of superheat before and after the plate heat exchanger constant.
(2) Heating-only Thermo-ON
When three minutes have passed after the LEV operates with initial opening, the LEV opening is adjusted every 1 minute to
keep the amount of subcool before and after the plate heat exchanger constant.
(3) Cooling-main/Heating-main Thermo-ON and Cooling-main/Heating-main refrigerant recovery
1) Periodic control for LEV1
The LEV opening is adjusted the same way as described in (2) Heating-only Thermo-ON and Heating-only refrigerant recov-
ery.
2) Periodic control for LEV2
To be fully open (3000)
Operation mode
SVM1
ON OFF
Cooling-only Thermo-ON
Always ON
Cooling-main Thermo-ON
Always OFF
Heating-only Thermo-ON
Always OFF
Heating-main Thermo-ON
Always OFF
Defrost
Always ON during heat recovery de-
frost
OFF except to perform heat recovery
defrost
Stop
Always OFF
Cooling-only Thermo-OFF
Always ON
Thermo-OFF (Heating-only, Mixture of
units in cooling and heating)
Always OFF
Cooling-only test run
Always ON
Test run for stop
Always ON
0000002394.book 73 ページ 2016年1月12日 火曜日 午後4時49分
Summary of Contents for CITY MULTI CMB-WP1016V-GA1
Page 1: ......
Page 9: ...HWE1410A GB ...
Page 11: ... 2 HWE1410A GB ...
Page 27: ... I Read Before Servicing 18 HWE1410A GB ...
Page 29: ... 20 HWE1410A GB ...
Page 47: ... 38 HWE1410A GB ...
Page 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Page 57: ... 48 HWE1410A GB ...
Page 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Page 69: ... 60 HWE1410A GB ...
Page 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Page 77: ... 68 HWE1410A GB ...
Page 95: ... 86 HWE1410A GB ...
Page 117: ... VII Test Run Mode 108 HWE1410A GB ...
Page 119: ... 110 HWE1410A GB ...
Page 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Page 209: ... 200 HWE1410A GB ...
Page 294: ......