1. Error
Code
Valve block fault
2. Error
definition and error detection method
Limit signal that is output from valve block is not detected or is not reset after it is detected.
3. Cause, check method and remedy
2512
Cause
Check method and remedy
(1)
Loose connectors, wiring fault
When the LEDs on the control board (VB3a-VB3p) are lit,
check the valve block whose LED is lit for loose connectors,
wiring fault, and proper operation. When the LEDs de-
scribed above are not lit, check all the valve block for proper
operation.
(2) Valve
block
fault
(3)
Control board fault
If no problems are found with the above items, replace the
control board.