V
Refrigerant Circuit ]
- 65 -
HWE1410A
GB
2. Sub-HBC
Part name
Symbols
Notes
Usage
Specifications
Check method
Thermistor TH31a~p
*1
,
TH32, 33
Water
side
Indoor unit circulating water con-
trol
Same as the table above
Valve
block
VB3a~p
*1
Water
side
1) Switches the water flow
path depending on the op-
eration mode
2) Temperature difference
control
Controls the water flow to
each indoor unit
DC12V
Opening of a valve driven by
a stepping motor
*2
*1. The names of port "a" through "p" are corresponding to port 1 through 16.
*2. For the degree of valve opening, "0" or "1600" indicates fully open and "800" indicates fully closed.