[7] Air Tightness Test (Refrigerant Circuit)
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)
Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an
HFC(R410A) leak.
Halide torch
R22 leakage detector
0000002394.book 9 ページ 2016年1月12日 火曜日 午後4時49分
Summary of Contents for CITY MULTI CMB-WP1016V-GA1
Page 1: ......
Page 9: ...HWE1410A GB ...
Page 11: ... 2 HWE1410A GB ...
Page 27: ... I Read Before Servicing 18 HWE1410A GB ...
Page 29: ... 20 HWE1410A GB ...
Page 47: ... 38 HWE1410A GB ...
Page 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Page 57: ... 48 HWE1410A GB ...
Page 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Page 69: ... 60 HWE1410A GB ...
Page 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Page 77: ... 68 HWE1410A GB ...
Page 95: ... 86 HWE1410A GB ...
Page 117: ... VII Test Run Mode 108 HWE1410A GB ...
Page 119: ... 110 HWE1410A GB ...
Page 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Page 209: ... 200 HWE1410A GB ...
Page 294: ......