VI
Control ]
- 78 -
HWE1410A
GB
Backup control
-9- Backup control
The following backup control is started on the HBC as necessary.
(1) Backup mode for plate heat exchanger protection
The following control is performed depending on the outlet pipe temperature of the plate heat exchanger for freeze-up pro-
tection.
[Cooling-main/Heating-main operation]
1) Outdoor unit (Heat source unit)
Cooling-main operation: Continued; Heating-main operation: Continued
2) HBC controller
(2) Heating water temperature backup mode
When the heating operation can be continued without receiving heat from the refrigerant due to water temperature rise during
heating operation (the outlet pipe temperature of the plate heat exchanger is 50ºC or above), the outdoor unit goes into the
Thermo-OFF mode, and the heating operation is performed only by circulating the hot water by the water pump. When the
water temperature decreases to a certain level (the outlet temperature of the plate heat exchanger is 45ºC or below), the out-
door unit starts up.
Water pump protection control
-10- Water pump protection control
When the circuit is clogged or air enters the water circuit, the protection control starts on the HBC controller to protect the
water pump and the system is stopped depending on the situation.
(1) When the internal temperature of the water pump increases
When the detection temperature of the water pump outlet pipe is above a certain level, the water pump is stopped to protect
it from the heat.
(2) When the revolutions of the water pump increases
When the revolutions of the water pump is above a certain level (The value changes depending on the specified voltage.),
the water pump is stopped to reduce the risk of air infiltration and water leaks.
Control mode
Cooling-main/Heating-main
Cooling-only
Outdoor unit
(Heat source
unit)
Operation
mode
Continues the current operation
Cooling-only Thermo-OFF
HBC controller 21S4Ma
Heating side: open (de-energized)
Cooling side: open (energized)
21S4Mb
Cooling side: open (de-energized)
Cooling side: open (de-energized)
LEV1
Maintains the opening that was used in the
previous operation mode
Opening during Cooling-only Thermo-OFF
LEV2
41 pulses: fully closed
Opening during Cooling-only Thermo-OFF
LEV3
3000 pulses: fully open
Opening during Cooling-only Thermo-OFF
SVM1
Closed
Open
PUMP1
Continues the heating operation
Continues the cooling-only operation
PUMP2
Continues the cooling operation
Continues the cooling-only operation
VB3a~p
The opening depending on the indoor unit
operation mode
The opening depending on the indoor unit
operation mode
body6.fm 78 ページ 2016年1月14日 木曜日 午後3時32分
Summary of Contents for CITY MULTI CMB-WP1016V-GA1
Page 1: ......
Page 9: ...HWE1410A GB ...
Page 11: ... 2 HWE1410A GB ...
Page 27: ... I Read Before Servicing 18 HWE1410A GB ...
Page 29: ... 20 HWE1410A GB ...
Page 47: ... 38 HWE1410A GB ...
Page 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Page 57: ... 48 HWE1410A GB ...
Page 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Page 69: ... 60 HWE1410A GB ...
Page 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Page 77: ... 68 HWE1410A GB ...
Page 95: ... 86 HWE1410A GB ...
Page 117: ... VII Test Run Mode 108 HWE1410A GB ...
Page 119: ... 110 HWE1410A GB ...
Page 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Page 209: ... 200 HWE1410A GB ...
Page 294: ......