ADDITIONAL REFRIGERANT CALCULATIONS (Y SERIES) example
4 - 45
S.D
. Y
MEE14K009
3. Piping Design
AN1 2nd
A
B
C
D
e
a
b
c
d
Indoor 1: P125
40 m
10 m
2: P100
10 m
5 m
3: P40
15 m
10 m
4: P32
10 m
10 m
5: P63
10 m
The total length of liquid pipe of each size is as follows:
ø12.7: A + e = 40 + 10 = 50 m
A: ø12.7
a: ø9.52
b: ø9.52
c: ø6.35
d: ø9.52
e: ø12.7
B: ø9.52
C: ø9.52
D: ø9.52
ø9.52: B + C + D + a + b + d = 10 + 15 + 10 + 10 + 5 + 10 = 60 m
ø6.35: c = 10 = 10 m
Example: PUHY-P350YKB
P40
P100
P125
P32
P63
=
+
+
+
+
+ 3.5
+
+
+
+
+ 3.5
+ 0
+ 0
(kg)
0 (m) x 0.26 (kg/m)
Additional
refrigerant charge
=
0
0
50 x 0.11
60 x 0.054
10 x 0.021
= 12.5 (12.45) kg
Total length of liquid
x 0.26 (kg/m)
0 (m) x 0.18 (kg/m)
Total length of liquid
x 0.18 (kg/m)
50 (m) x 0.11 (kg/m)
Total length of liquid
x 0.11 (kg/m)
60 (m) x 0.054 (kg/m)
Total length of liquid
x 0.054 (kg/m)
10 (m) x 0.021 (kg/m)
Total length of liquid
x 0.021 (kg/m)
Maximum refrigerant charge
Amount of factory charged refrigerant
There is a limit to the amount of refrigerant that can be charged into a unit. Regardless of the amount yielded by the formula above, observe the maximum
refrigerant charge in the table below.
Total index of the
outdoor units
P200YKB
22.3kg
P250YKB
29.7kg
P300YKB
32.7kg
P350YKB
33.6kg
P400YSKB
45.0kg
P450YSKB
45.9kg
P500YSKB
47.0kg
P550YSKB
51.3kg
P600YSKB
53.9kg
P650YSKB
56.5kg
P750YSKB
68.9kg
Maximum *1
refrigerant charge
*1 Maximum refrigerant charge: the amount of factory-charged refrigerant and the amount of refrigerant to be added on site
P700YSKB
68.9kg
Total index of the
outdoor units
P800YSKB
71.4kg
P850YSKB
73.2kg
P900YSKB
75.7kg
P950YSKB
96.9kg
P1000YSKB
99.9kg
P1050YSKB
102.9kg
P1100YSKB
106.0kg
P1150YSKB
109.0kg
P1200YSKB
112.0kg
P1250YSKB
112.0kg
P1300YSKB
112.0kg
P1350YSKB
112.0kg
Maximum *1
refrigerant charge
8.0kg
6.5kg
11.5kg
11.8kg
P200
P250
P300
P350
P400
P450
Outdoor unit
model
Charged amount
0000003416.BOOK 45 ページ 2014年11月11日 火曜日 午前9時34分
Summary of Contents for BDT CITY MULTI
Page 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...
Page 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...
Page 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...
Page 47: ...47 ...
Page 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...
Page 63: ...63 DIP SWITCHES INDOOR UNITS ...