INDOOR UNIT INSTALLATION SETTINGS
The loose pages in the back of this booklet have indoor unit setting information. These pages must be completed prior to BDT
attending site for commissioning. If additional installation setting sheets are required please contact your BDT sales representative.
MODEL:
SERIAL:
GROUP NAME:
Please circle the address and dip switch settings
0 1 2
3
45
67
8
9
0 1 2
3
45
67
8
9
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
OFF
ON
SW1
1
Room temperature detection position
Indoor unit inlet
Built-in sensor on the
remote controller
While the unit is
stopped (Remote
controller OFF)
2
Clogged filter detection
Not available
Available
3
Filter check reminder time setting
100h
2500h
4
Outside air intake
Disabled
Enabled
5
Remote display option
Fan output
Thermo - ON signal
6
Humidifier control
During heating
operation
Always on while in
the heating mode
7
Fan speed setting for Heating Thermo - OFF
Very low
Low
Forced heating operation at OA temp of 5
°
C
or below
Not available
Available
8
Fan speed setting for Heating Thermo - OFF
According to the
SW1-7 setting
Pre-set speed
-
-
-
9
Self-recovery after power failure
Disabled
Enabled
10
Power source start-stop
Disabled
Enabled
SW3
1
Unit model selection
Heat pump
Cooling only
2
Louvre
Not available
Available
3
Vane
Not available
Available
4
Vane swing function
Not available
Available
5
-
-
-
6
Vane angle limit setting for cooling operation
Down blow B,C
Horizontal
Initial vane position
Enabled
Disabled
7
Automatic LEV value conversion function
Not available
Available
8
Heating 4
°
C [7.2°F] up
Enabled
Disabled
9
SHm setting
2°C [3.6°F]
5°C [9°F]
10
SCm setting
10°C [18°F]
15°C [27°F]
Quote Number
Job Name
INDOOR UNIT INSTALLATION SETTINGS template
Summary of Contents for BDT CITY MULTI
Page 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...
Page 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...
Page 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...
Page 47: ...47 ...
Page 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...
Page 63: ...63 DIP SWITCHES INDOOR UNITS ...