4-2. Integrated Centralized Control settings are not set correctly
Monitoring and operation using Integrated Centralized Control Web are not possible for a centralized controller
whose integrated centralized control settings have not been configured using Initial Setting Tool.
Important
●
Check that the centralized controllers that are control targets of Integrated Centralized Control Web are registered correctly
using Initial Setting Tool. Refer to the Instruction Book (Initial Settings) for details.
(1) Click [Basic Settings] > [System Configuration] in Initial Setting Tool to open the System Configuration settings
screen.
(2) Enter the IP addresses of all the centralized controllers that are control targets of Integrated Centralized
Control Web and then click [Save].
(3) Click [Acquire data] from the [Data acquisition] menu to acquire the information on the air conditioning cooling
and heating integrated centralized control system.
(4) Click [Floor Settings] > [Floor for Integrated Centralized Control Web] to open the Floor for Integrated
Centralized Control Web settings.
(5) Check the centralized controllers displayed in “Managed centralized controller.”
* Any centralized controller without a check mark is not a control target of Integrated Centralized Control Web.
System Configuration settings
Floor settings for Integrated
Centralized Control Web
Acquire
data
Managed centralized controllers
Chapter 5
Troubleshooting