![Mitsubishi Electric AE-200A Instruction Book Download Page 116](http://html.mh-extra.com/html/mitsubishi-electric/ae-200a/ae-200a_instruction-book_1810107116.webp)
116
WT07996X02
1-1-5. Advanced settings
In the group list, selecting the group icon(s) and clicking [Advanced] in the taskbar will bring up the operation
settings screen for the selected group(s). The current operation status will appear.
Change necessary operation settings, and then click [Send] to reflect the changes. Click [Close] to return to the
previous screen without making any changes.
Note: When the setting is changed from other controllers, the operation status shown on the screen will not be updated while the
screen is open.
[1] Air conditioning unit group
Item
Operation method
Description
ON/OFF
Select [ON] or
[OFF].
Turns on or off the units.
Operation
mode
Select an operation
mode.
Click the desired operation mode.
[Cool], [Dry], [Fan], [Heat], [Auto], [Setback]
Note: When the operation mode signals from the cooling/heating switchover model of
units are mixed (Cool and Heat), the operation mode will not change.
Note: The Setback mode can be selected on the AE-200A/AE-50A/EW-50A, but not
on the AE-200E/AE-50E/EW-50E.
Set
temperature
Adjust the set
temperature with
the
buttons.
Depending on settings values resulting from restrictions by device functions and
set temperature range restriction functions, temperature settings ranges may be
restricted.
Note: For the same indoor unit, when changing operation mode and set temperature
from multiple operation devices (system controllers, remote controllers), display
of outside the allowable settings range may occur.
Note: Depending on the unit model, setting in 0.5°C units and 1°C units is possible.
Note: If the indoor unit supports the dual-set-point function in the Auto mode and
when the operation mode above is set to Auto or Setback, two set temperatures
for Cool mode and Heat mode can be set. For details about the dual-set-point
Note: When the indoor units that support the dual-set-point function and the indoor
units that do not support the dual-set-point function exist in the same group,
only one set temperature can be set in the Auto mode.
Air Direction
Adjust the air
direction with the
buttons.
Auto
Swing
Fan Speed
Adjust the fan speed
with the
buttons.
Auto
Interlocked
LOSSNAY
ON/OFF
Select [ON] or
[OFF].
Turns on or off the interlocked LOSSNAY units (ventilator).
Set temperature
Close
Click to close the settings
screen without making any
changes.
Send
Click to reflect
the changes
made.
Close
Click to close the settings
screen without making any
changes.
Fan Speed
Filter Sign Reset
Click to reset the
filter sign.
Send
Click to reflect the
changes made.
Group name
ON/OFF
Operation
mode
Air Direction
Interlocked
LOSSNAY
ON/OFF
Fan speed of
interlocked
LOSSNAY
Hold
Schedule
Prohibit Remote
Controller Operation