Note: About Optimized Start function
The Optimized Start function will start the units 5 to 60 minutes prior to the scheduled start time to reach the set temperature at
the scheduled start time. To use this function, select [Optimized Start] on the schedule contents settings screen.
•
When the units start the first time after a power reset, the units will start operation 30 minutes before the scheduled start
time.
•
If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the measured value
may not be an accurate representation of the temperature in the room. When this is the case, use an external temperature
sensor (PAC-SE40TSA) or remote controller sensor to measure the room temperature.
•
[Optimized Start] can be selected only for air conditioning units and Air To Water units.
9:00
8:45
9:00
8:40
26ºC
24ºC
[5] Saving the schedules
(1) After the schedule settings are completed, click [Send] on the Schedule settings screen to send and save
the settings to the centralized controllers.
To undo the changes made, click [Cancel].
Note: Clicking [Send] will send the schedule settings to the centralized controllers (AE-200/AE-50/EW-50). It may take a few minutes
to complete the transmission, depending on the volume of the schedule contents.
Cool ON
Operation mode: Cool
Start time: 9:00
Set temperature: 26ºC
Room
temperature
Heat ON
Operation mode: Heat
Start time: 9:00
Set temperature: 24ºC
Room
temperature
Cancel
Click to undo the changes
made and close the Schedule
settings screen.
Send
Click to save the settings.
Schedule settings