26
Installing the NC-2000 Patient Unit
•
If your paging amplifier outputs 75 V, connect the outputs on the paging amplifier to the
HIGH and COM inputs on CN2.
Figure 18 Paging amplifier - 75 V output
3.6 Bed Cords
The Patient Unit has two 0.25 inch jacks for bed cords. Each jack is supervised.
•
If two bed cords are being used, close the jumper shown in Figure 19.
•
If only one bed cord is being used, insert a 0.25 inch dummy plug in the unused jack and
close the jumper shown in Figure 19.
•
If no bed cords are being used, open the jumper shown in Figure 19.
Figure 19 Bed cord input terminal CN3
Paging Amplifier
75V output
22AWG
COM
HIGH
COM
C
75V
NC-2000
CN2
COM
HIGH
NC-2000
CN2
COM
HIGH
NC-2000
CN2
HIGH
NC-2000
CN2
Jumper