Technical data
Description
Data
Internal connection
Pin strip, 50
‑
pin
External connection
9
‑
pin D
‑
Sub female connector in module cover
Transfer rate
9.6 kbit/s to 12 Mbit/s, baud rate auto-detection
Connection mode
ProiBus network,
connections can be made/released without afecting other
stations.
Protocol
PROFIBUS-DP-V0 SLAVE to IEC 61158
Coniguration
GSD ile
"SART_5500.gsd"
Potential isolation
Yes, optocoupler in lines A and B (RS-485)
Bus termination
The bus termination in the last device is implemented via the
integrated terminating resistor in the ProiBus plug.
Cable type
ProiBus "special"; color: violet; screened twisted pair cable
Cable impedance
150
Ω
Cable length
The max. distance of 200 m can be extended at 1.5 Mbit/s by
means of an additional repeater.
Dimensions (LxWxH)
55x50x22 mm
Weight
Approx. 33 g
Certiicates
Proibus test center Comdec in Germany and PNO (Proibus
User Organization).
Industry-compatible CE, UL, and cUL
Note:
The GSD ile is stored on the CD supplied with the device (ieldbus directory of the
respective device). The current ile is also available to download online:
http://www.minebea-intec.com
4 Device installation
Process Controller Maxxis 4 PR 5500
Minebea Intec
EN-81