4.5.10 CC-Link interface
The CC-Link interface card has the type designation PR 1721/65.
The ieldbus card contains all functions to provide a complete CC-Link slave with transfer
rates up to 10 Mbps.
The CC-Link connection is established by the 5-pin terminal.
The card is inserted in the Option 1/FB slot, see Chapter
.
Technical data
Designation
Data
Internal connection
Pin strip, 50
‑
pin
External connection
5
‑
pin terminal (plug-in) in the module cover
Transfer rate
156; 625 kbps; 2.5; 5, 10 Mbps
Protocol
CC-Link slave
-
CRC error recognition according to IEC 62026 (EN 50325)
-
Max. 64 station nodes
-
128 I/O bits and 16 (32 bit) words
Coniguration
CSPP ile "0x0608_Maxxis_4_1.00_en.CSPP"
Potential isolation
Yes, optocoupler and DC/DC converter
Bus termination
110
Ω
at the cable ends
Bus load
100 mA
Cable type
2x2 screened twisted pair
Cable length
100 m @ 10 Mbps, 1200 m @ 156 kbps
Dimensions (LxWxH)
55x50x22 mm
Weight
Approx. 33 g
Certiicates
-
Type: ABCC-CCL (CC-Link CARD)
(H/W: from 1.03, S/W: from 1.03, CC-Link: 1.10)
-
Reference no.: 1102
Note:
The CSPP ile is stored on the CD supplied with the device (Fieldbus directory of the
respective device). The current ile is also available for download via the Internet:
http://www.minebea-intec.com
Process Controller Maxxis 4 PR 5500
4 Device installation
EN-88
Minebea Intec