Technical data
Description
Data
Internal connection
Contact strip
External connection
2× terminal, 6-pin
2× terminal, 4-pin
Wire gauge max. 1.5 mm
2
Number of inputs
6 (CH1, CH2, CH3, CH4, CH5, CH6)
Input voltage
Low: 0 to 5 V
High: 10 to 28 V
Passive, external power supply required
Input current
<7 mA @ 24 V
<3 mA @ 12 V
Number of outputs
8 (CH1, CH2, CH3, CH4, CH5, CH6, CH7, CH8)
Output supply voltage
Max. 24 V +10% external to connector
Output voltage drop
I_Load * 55
Ω
+1 V (output conducting)
Output max. switching cur-
rent
25 mA
Signals
GND (-) common for all inputs and outputs
Potential isolation
Yes, via optocoupler
Cables
Screened
Connect cable screen to the device.
Cable length
Max. 50 m
Dimensions (L×W×H)
52×52×19 mm
Weight
50 g
Process Controller Maxxis 4 PR 5500
4 Device installation
EN-74
Minebea Intec