Technical data
Description
Data
Internal connection
Contact strip
External connection
2× terminal, 6-pin
2× terminal, 4-pin
Wire gauge max. 1.5 mm
2
Number of inputs/out-
puts
4 (CH1, CH2, CH3, CH4)
Input
Can be switched via a potential-free contact
Input frequency
Max. 200 Hz
Output
Change-over contact
Max. switching voltage:
U
DC
= 31 V/U
AC
= 24 V
Max. switching current:
1 A
Switching frequency
Max. 0.5 Hz
Potential isolation
Inputs:
Jointly supplied via potential-free voltage
Outputs:
Free relay change-over contact
Cables
Screened
Connect cable screen to the device.
Cable length
Max. 50 m
Dimensions (L×W×H)
60×106×22 mm
Weight
70 g
Process Controller Maxxis 4 PR 5500
4 Device installation
EN-68