Example:
Connection for PR 5500/13: Voltage output
①
2.2 k
Ω
/1 k
Ω
with 24 V/12 V
②
Grounding terminal or screen clamping rail
③
U
DC
= 24 V 0.5 A power supply unit
When the output is active (true), the output voltage drops from 24 V/12 V to 0 V. The
load resistance must be 2.2 k
Ω
/1 k
Ω
.
4.5.7
PR 5500/17 digital inputs and outputs
The plug-in card has 6 passive opto-decoupled inputs and 8 passive opto-decoupled
outputs for process control.
All inputs and outputs have a common GND (-).
The card is inserted in the option 1/FB and/or option 2 slot.
A maximum of 2 PR 5500/17 plug-in cards can be installed.