Certificates and Approvals
The Intrinsical Safety Specifications of the MST9500 have been defined and approved as
follows:
Application
Application
Application
Application
Specifications
Specifications
Specifications
Specifications
current loop insulated from the measuring circuit
3.6-22 mA
internal capacitance
can be neglected
internal inductance
10 µH
maximum supply voltage
30 Vdc
maximum current
200 mA
maximum power consumption
1.5 W
The MST9500 can be directly connected to an intrinsically safe supply for intrinsically safe
applications. For non-intrinsically safe operations, such as explosion proof, a safety barrier
must be used.
The operation of the MST9500 conforms to the following:
NAMUR recommendation NE 43
This recommendation describes rules with which analogue transmitters transfer their
information to D.C.S. equipment. This information can be divided into the following types:
•
measurement information and failure signalling
As far as measurement information
measurement information
measurement information
measurement information is concerned, it is indicated that the current
signal should be in the range of 3.8
3.8
3.8
3.8 to 20.5
20.5
20.5
20.5 mA
mA
mA
mA.
•
Failure information
Failure information
Failure information
Failure information which indicates a failure in the measuring system applies to
the current ranges of 0
0
0
0 to 3.6
3.6
3.6
3.6 mA
mA
mA
mA and 21
21
21
21 mA
mA
mA
mA or greater.
The application will determine which of these two failure ranges is desirable. The
MST9500 can be set for one of them as required.