Command #144 Reset Recorded P.V. Max./Min. Values
This command rests the recorded maximum and minimum values for PV back to a start value,
in this case, the current PV value.
Request data bytes
None
Return data bytes
None
Command # 145 Read Recorded P.V. Max./Min. Values
This command returns the recorded maximum and minimum values for PV since the last reset
command or the last power cycle.
Request data bytes
None
Return data bytes
Data byte
#0
P.V
Range Units
Code
#1
PV
Max Recorded
Value
MSB
#2
#3
#4
PV
Max Recorded
Value
LSB
#5
P.V
Min. Recorded
Value
MSB
#6
#7
#8
P.V
Min. Recorded
Value
LSB
Data byte #0
P.V. Units Code, 8-bit unsigned integer
Data byte #1-#4
P.V Max. Recorded Value, IEE754
Data byte #5-#8
P.V Min. Recorded Value, IEE754