Page 20
MERCAP – INSTRUCTION MANUAL
7ML19981CM01.1
A similar example in inches yields the following:
C
increase for oil
=
ξ
r
_oil-
ξ
r
_air 7.32x4.5 = 16.6 pF
Log (60/0.63)
So for this slightly larger tank, the
capacitance ranges from 16.6 pF to 33.2 pF.
So on calibration:
16.6 pF
≅
0%
≅
4 mA or 20 mA
33.2 pF
≅
100% 20 mA or 4 mA
Mercap
6" (0.5ft)
L = 54"
(4.5ft)
60"
(5.0ft)
d = 0.63"