7ML19981CM01.1
MERCAP – INSTRUCTION MANUAL
Page 45
sent to the transmitter will be saved automatically in the non-volatile memory upon receipt of
the Write or Set Command. Command #39, EEPROM Control, is not implemented.
MultiDrop operation
This revision of the MST9500 transmitter supports MultiDrop Operation.
Burst mode
This revision of the MST9500 transmitter does not support Burst Mode.
Units conversions
The Primary Variable Units are in pF and cannot be changed. The Primary Variable Sensor
Limits are also in pF and the same for the Primary Variable Range Values.
The Secondary Variable Range Values may be set to any Units and Value with Command
#140. The S.V. Range Values may be read at any time with Command #141.
The value returned as S.V. is the result of the following calculation:
S.V. = P.V. Range in percent x (SVURV - SVLRV) + SVLRV.
This method provides a means to transfer the P.V. which is always in pF, to an alternative
level- or contents value.
Additional universal command specifications
Command #3 Read Dynamic Variables and P.V. Current
The Primary Variable returns the Transmitter Variable #0 always in pF.
The Secondary Variable returns the Transmitter Variable #1 which is the Alternative Range
Value.
Additional common-practice command specifications
The MST9500 implements a subset of the Common Practice Commands specified in the
Common-Practice Specification document. This section contains information pertaining to
those commands that require clarification.
Command #35 Write Primary Variable Range Values
The Primary Variable Range Unit Codes will only accept units in pF.