![Milltronics Mercap MCP01 D series Instruction Manual Download Page 31](http://html1.mh-extra.com/html/milltronics/mercap-mcp01-d-series/mercap-mcp01-d-series_instruction-manual_1796996031.webp)
7ML19981CM01.1
MERCAP – INSTRUCTION MANUAL
Page 29
Whenever the local situation allows, the zero adjustment and the full scale can be recorded
with the press of a button. Furthermore, the HART
TM
implementation allows for adjustment of
the MST9500 according to specific requirements.
The galvanic isolation between the measuring circuit and current loop provides immunity
during the use of cathode protected measuring tanks. Connection to PLC equipment is
possible without any problems.
Factory Settings
The MST9500 has a number of default factory settings. If the required settings for the
application are known, the settings can be modified during final testing.
Settings:
Setting
Setting
Setting
Setting
Description
Description
Description
Description
ID
has a unique serial number
PV Units
pF
USL(PV)
3300 pF
LSL(PV)
1.666 pF
URV(PV)
3300 pF [switch. position 2]
LRV(PV)
0.00 pF [switch. position 1]
AO1(PV)
4-20 mA is 0-100%
TAG
"customer input data via HART"
DESCRIPTOR
"customer input data via HART"
MESSAGE
"Milltronics"
DATE
"customer input data via HART"
SENSOR SERIAL NUMBER
"customer input data via HART"
FINAL ASSEMBLY NUMBER
"customer input data via HART"
SV Units
UNDEFINED
SVLRV
0
SVURV
1.0
As the USL and LSL are set to 3300 respectively 1.666 pF, the following applies:
•
The MST9500 can be adjusted with the push-button. The URV and LRV, which
should be inside
inside
inside
inside the USL and LSL, can be set anywhere in the entire range.
•
Interruption of the measuring connection is detected. A loose or interrupted
connection results in to up to 0.5 pF capacity, which is below the adjusted LSL.
Siemens Automation