7ML19981CM01.1
MERCAP – INSTRUCTION MANUAL
Page 47
Transmitter specific commands
Command #128 Set Alarm Select
This command specifies the state of the Primary Variable Analog Output in case of device
malfunction. The status of this variable is returned in byte #0 with Command #15 Read Primary
Variable Output Information.
This command accepts only the values 0 or 1 resp. Alarm Select High or Alarm Select Low.
Request data bytes
Data bytes
#0
Alarm
Select
Code
Data byte
#0
Alarm Select Code, 8-bit unsigned integer,
Selection may be either 0 or 1.
Response data bytes
Data bytes
#0
Alarm
Select
Code
Data byte
#0
Alarm Select Code, 8-bit unsigned integer,
Refer to Alarm Selection Codes, table VI.
Command #129 Adjust for Product Build-Up on Sensor
This command sets the lowest of LRV/URV equal to the actual P.V. value.
This compensates for shift in LRV (0-100% range) or URV (100-0% range) due to product-build-
up on the sensor.
Request data bytes
None
Response data bytes
None