OM-2226 Page 25
4-15. Electrical Service Guide
.
Actual input voltage should not fall below 103 volts AC or rise above 506 volts AC. If actual input voltage is outside this range, unit may not operate
according to specifications.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
Input Voltage (V)
Single-Phase,
100% Duty
Cycle
Single-Phase,
60% Duty
Cycle
Three-Phase, 60% Duty
Cycle
115
230
230
400
460
Input Amperes (A) At Rated Output
25
22
13.1
7.4
6.4
Max Recommended Standard Fuse Rating In Amperes
1
Time Delay Fuses
2
25
25
15
8
8
Normal Operating Fuses
3
35
30
20
10
10
Min Input Conductor Size In AWG
4
10
12
14
14
14
Max Recommended Input Conductor Length
In Feet (Meters)
57 (17)
79 (24)
102
(31)
308
(94)
407
(124)
Min Grounding Conductor Size In AWG
4
10
12
14
14
14
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.