ANYBUS - ERROR LIST
ProfiNet IP
#
Item
1
Network status LED
2
Module status LED
3
Link/Activity LED
4
Ethernet Interface
Network Status LED
Note:
A test sequence is performed on this LED during startup
LED State
Description
Comments
Off
Offline
- No power
- No connection with IO Controller
Green
Online (RUN)
- Connection with IO Controller established
- IO Controller in RUN state
Green, flashing
Online (STOP)
- Connection with IO Controller established
- IO Controller in STOP state
Module Status LED
Note:
A test sequence is performed on this LED during startup
LED State
Description
Comments
Off
Not Initialized
No power - or - Module in ‘SETUP’ or ‘NW_INIT’ state
Green
Normal Operation
Module has shifted from the ‘NW_INIT’ state
Green, 1 flash
Diagnostic Event(s)
Diagnostic event(s) present
Green, 2 flashes
Blink
Used by engineering tools to identify the node on the network
Red
Exception Error
Module in state ‘EXCEPTION’
Red, 1 flash
Configuration Error
Expected Identification differs from Real Identification
Red, 2 flashes
IP Address Error
IP address not set
Red, 3 flashes
Station Name Error
Station Name not set
Red, 4 flashes
Internal Error
Module has encountered a major internal error
LINK/Activity LED
LED State
Description
Comments
Off
No link
No link, no communication present
Green
Link
Ethernet link established, no communication present
Green, flickering
Activity
Ethernet link established, communication present
Ethernet Interface
The Ethernet interface operates at 100 Mbit, full duplex, with autonegotiation enabled as default.