9.2.1.5 Output channels
9.2.1.5.1 Basis
Unit
Selection of the time unit for the ext. Warmup time
Milliseconds
The output channel is switched on "Ext warmup time" milliseconds prior to the
measurement.
Seconds
The output channel is switched on "Ext warmup time" seconds prior to the
measurement.
Ext warmup time
Indicates the amount of time that an output channel is switched on in "Ext warmup time" mode before
the measurement
Title 1
Freely selectable channel title for the switchable sensor supply
Mode
Basic setting for the output channel
Off
Output channel deactivated
Ext warmup
time
The output channel is switched on prior to each measurement. How long before the
measurement, the output channel is switched on is specified via the "Unit" and "Ext
warmup time" parameter. If the "Ext warmup time" value is "0", the output channel is
not switched on at all. A detailed description is provided in chapter "Technical
details about the "switchable sensor supply (Vout)"" on page 54.
9.2.1.6 Internal channels
9.2.1.6.1 Basis
Battery title
Freely selectable channel title for the battery voltage
Unit
String that is used as a measurement unit by all of the server display elements
[0-16 characters]. It has no direct influence on the values
GSM level title
Freely selectable channel title for the GSM level
Unit
String that is used as a measurement unit by all of the server display elements
[0-16 characters]. It has no direct influence on the values
9.2.1.6.2 Alarms
Warning
Value low
A warning is triggered, if the measurement value drops to or below this value.
Value high
A warning is triggered, if the measurement value meets or exceeds this value.
Alarm
Value low
An alarm is triggered, if the measurement value drops to or below this value.
Value high
An alarm is triggered, if the measurement value meets or exceeds this value.
Hyst %
Hysteresis for the all-clear in the event of an alarm/warning (e.g. Hyst = 5%, alarm or warning
at 100 -> all-clear at 95) or reset the trigger (e.g. Hyst = 5%, level = greater or equal, trigger at
100 -> reset at 95)
84
Rev. 02
Summary of Contents for myDatalogNANO
Page 2: ......
Page 8: ......
Page 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 02 9 ...
Page 10: ......
Page 12: ......
Page 22: ......
Page 34: ......
Page 38: ......
Page 58: ......
Page 92: ......
Page 108: ......
Page 118: ......
Page 120: ......
Page 126: ......
Page 130: ......