GB
FS 345 Door Controls / Rev.A 0.0 – 25
9.4 LED indications of the FS101
The FS 345 control unit is equipped with a row of LEDs that indicate the current operating status of the system and indicate any faults
that may occur. The following table gives an overview of the various faults and status conditions.
K04 K05
K06 K07 K08
K09
K10
K11
K12
F
S
1
0
1
-P
1
-1
D018 D017 D016
D02
D01
D03
D04
D05
D06 D07 D08 D09
D010 D011
D012
D013
D014
D015
D019
9.5 LED diagnostic FS 101
Code
Colour
Description
Error diagnosis
D01
yellow
LED safety circuit
(input X03/1,2)
LED ON
LED OFF
OK
- No power supply from mains or rechargeable battery
- Operator safety circuit interrupted
D02
yellow
LED limit switch OPEN
(input X03/3,4,5)
LED ON
LED OFF
Limit switch OPEN not confirmed
Limit switch OPEN confirmed
D03
yellow
LED limit switch CLOSED
(input X03/6,7,8)
LED ON
LED OFF
Limit switch CLOSED not confirmed
Limit switch CLOSED confirmed
D04
yellow
LED auxiliary motor
(output X04/1,2)
LED ON
LED OFF
Auxiliary motor is active
Auxiliary motor 24V DC is not active
D05
yellow
LED motor brake (output
X04/3,4)
LED ON
LED OFF
Motor brake is switched on
Motor brake is switched off
D06
yellow
LED drive command open/
close
(output X04/ 5,6)
LED ON
LED OFF
Drive command open/close on CS 300 FS is active
Drive command open/close on CS 300 FS is not active
D07
yellow
LED limit switch OPEN
(output X05/1,2)
LED ON
LED OFF
Limit switch OPEN not confirmed
- Limit switch OPEN confirmed
- Emergency operation is active
D08
yellow
LED limit switch CLOSED
(output X05/3,4)
LED ON
LED OFF
Limit switch CLOSED not confirmed
Limit switch CLOSED confirmed