FS 345 Door Controls / Rev.A 0.0 – 13
5.10 DIP switches:
1 ON Door operator types FT (+ HY)*
1 OFF Door operator types FDF + FTA
2 ON Fire alarm as normally open contact
2 OFF Fire alarm as normally closed contact
3 ON Emergency closing with 400V AC / 24 VDC
3 OFF Emergency closing with 24V DC
4 ON With CESD (SKS) in emergency operation
4 OFF Without CESD (SKS) in emergency operation
5 ON Door closes if an error occurs
5 OFF Door remains open if an error occurs
6 ON (Operator type HY)*
6 OFF Operator type FT
When making changes to the DIP switch settings, the follow
-
ing procedure must be observed:
1.
Switch off the mains voltage
2.
Switch off the rechargeable battery voltage
3.
Change the DIP switch positions as required
4.
Switch on the rechargeable battery voltage
5.
Switch on the mains voltage
* version HY only
5.11 Types of door operator
The FS 345 control is designed for use with two different
types of door operator.
FT operators
DIP 1 ON and DIP 6 OFF
1. FT door operators with 24V DC motor
braking.
In emergency mode, the door is closed via the
24V DC auxiliary motor.
The weight of the door is held by the ener-
gised motor brake.
The power supply comes from the mains
adapter on the FS 101 circuit board; if the
mains power is interrupted, power is supplied
from the rechargeable battery.
(DIP 6 ON required for version HY)
FD (FDF, FTA, FDS) operators
DIP 1 OFF
1. FD (FDF, FTA and FDS) door operators with
a 24V DC auxiliary motor and 24V DC motor
brake (FDF 5). In emergency mode, the door is
closed via the 24V DC auxiliary motor.
The power supply comes from the mains
adapter on the FS 101 circuit board; if the
mains power is interrupted, power is supplied
from the rechargeable battery.