36 – FS 345 Door Controls / Rev. A 0.0
12. Technical data
12.1 Mechanical and electrical data
Housing dimensions:
750 x 300 x 132 mm
Installation:
Vertical mounting on the wall,
minimum height above floor = 1,100 mm
Supply voltage:
3~ 400 V AC, 50 Hz, +/- 10% STANDARD
3~ 230 V AC, 50 Hz, +/- 10% SPECIAL SOLU
-
TION
Other voltages on request
Fuse protection:
10 A K type
Power input:
Max. 2.2 kW
Internal consumption
of control:
Max. power consumption of the CS 300 FS
control itself = 250 mA on secondary side
Max. power consumption of the FS 101control
itself = 200mA on secondary side
Motor data:
max. 2.2 kW AC / -3.2 A.
Control voltage:
24 V DC, all input connections must be
potential-free; minimum signal duration for
input control command >100 ms
Control outputs:
24 V
DC
, maximum of 500 mA
Batteries
Maintenance-free batteries with VdS certifica
-
tion
Fault output relay:
If inductive loads are connected (e.g. further
relays or brakes), these must be fitted with ap
-
propriate suppressor elements (recovery diodes,
varistors, RC circuits).
Potential-free normally open contact; min.
10mA ; max. 230 V 230V AC ~ 4A
Once contacts have been used for power cir-
cuits, they can no longer be used for extra-low
current circuits.
Emergency operation
output relay:
If inductive loads are connected (e.g. further
relays or brakes), these must be fitted with ap
-
propriate suppressor elements (recovery diodes,
varistors, RC circuits).
Potential-free normally open contact; min.
10mA ; max. 230 V 230V AC ~ 16A
Once contacts have been used for power cir-
cuits, they can no longer be used for extra-low
current circuits.
Temperature range:
Operation: +5°C … +55°C
Storage:
-20°C … +85°C
Air humidity:
Up to 80% with no condensation
Vibrations:
Low-vibration mounting, e.g. on a masonry wall
Type of protection:
IP 54
Weight:
approx. 10.5 kg
13. Maintenance
The FS 345 control is maintenance-free.
DANGER!
Life-threatening danger due to electric shock!
The control unit or door system MUST be disconnected
from the electricity supply before carrying out any electri-
cal work. Take measures to ensure that the power supply
remains disconnected for the duration of the work.
The following points must be taken into account when carry-
ing out maintenance on the door system:
Maintenance must only be carried out by authorised persons.
Directive ASR A1.7 must be complied with.
Worn or faulty parts must be replaced.
Only approved parts may be installed.
All maintenance work must be documented.
Replaced fault parts must be disposed of properly in accord-
ance with the materials they contain and local regulations.