28 – FS 345 Door Controls / Rev. A 0.0
9.7 Adjustment options for TIME 1 (door
closes if the mains supply fails)
With timer 1, the control can delay the automatic closing of
the door after mains power failure by a set period. When set
to 0, the door does not close automatically in the event of
mains failure.
If the timer is set to 0 and the mains supply is cut off for a
longer period, the deep discharge protection system for the
control comes into play. See 17.1.
0 - No automatic closing in the event of mains failure
1 - In the event of a power cut: closes after 5 seconds
2 - In the event of a power cut: closes after 15 seconds
3 - In the event of a power cut: closes after 30 seconds
4 - In the event of a power cut: closes after 1 minute
5 - In the event of a power cut: closes after 2 minutes
6 - In the event of a power cut: closes after 5 minutes
7 - In the event of a power cut: closes after 15 minutes
8 - In the event of a power cut: closes after 30 minutes
9 - In the event of a power cut: closes after 60 minutes
9.8 Automatic mode with active closing edge
safety device in emergency operation
It is possible to monitor emergency operation with a contact
bar. If the contact bar is triggered, the door stops in emergen
-
cy operation. After the contact bar is free again and a delay
of 2 seconds has elapsed, emergency closing is continued.
Reversing does not take place. The function of the closing
edge safety device (SKS) is checked in the upper end position.
If a discernible error is detected, emergency operation takes
place without an evaluation of the SKS.
Prerequisites:
− CS 300 FS is connected to FS 101 (see drawing)
−
Relay mode 19 is set for relay 4 (factory setting)
− FS 101 DIP switch 4 is ON (switch off mains voltage and
battery power)
− CESD (SKS) is connected to terminal X4 of CS 300 FS
Connection between CS 300 FS + FS 101
7
8
X5
K05 K06 K07 K08 K09
+
-
24 V DC
Relay 4
CS 300 FS
Battery
FS101
Overview of functions