FS 345 Door Controls / Rev.A 0.0 – 23
9.2 Input operating mode
Function
Description
Setting options
Factory settings
GERMAN
Select the menu language
DEUTSCH
ENGLISH
FRANCAIS
NEDERLANDS
ESPANOL
POLSKI
CESKY
DEUTSCH
RUNTIME
Monitoring the maximum running time for an open and closing movement.
1 – 250 seconds
60 seconds
OPEN TIME
After the door has opened, it runs back in the CLOSE direction after the set time has
elapsed.
Open time > 0 = impulse functions only work in the OPEN direction
0 – 600 seconds
0 = Auto close off
PREWARN
-
ING
The warning light flashes before the door starts to close. The preset warning time is
only active if the open time is > 0 or if operated via radio impulse.
0 - 120 seconds
0 = Off
REVERS.
TIME
Standing time at every change of direction
0.1 - 2.0 seconds
(in 1/10 seconds)
0.3 seconds
MOD 1-3
STANDBY
MOD1:
When resting OFF
MOD2:
When resting ON
MOD1
MOD2
MOD1
QUICK
CLOSE
ON: The open time is cut short after the photoelectric barrier has been passed (door
closes immediately).
OFF: The open time continues as usual.
ON
OFF
OFF
RELAY 1
A relay module from 1 - 18 can be assigned to the first three relays.
MOD1: Red light is on during door movement and flashes as advanced warning
MOD2: Red light flashes during door movement and flashes as advanced warning
MOD3: Red light flashes during door movement and flashes as advanced warning
The parameter M3–1 STAND. affects these 3 MOD.
MOD4: Impulse when there is an OPEN command
MOD5: Error message
MOD6: OPEN end position
MOD7: CLOSED end position
MOD8: OPEN end position negated
MOD9: CLOSED end position negated
MOD10: Before-end position OPEN
MOD11: Before-end position CLOSED
MOD12: Before-end position CLOSED to CLOSED end position
MOD13: Magnetic lock function
MOD14 Brake
MOD15: Brake negated
MOD16: Brake remains ON during open time
MOD17: Brake remains ON during open time and direction turnaround
(with a CESD (SKS) the brake is deactivated)
MOD18: Red light flashes as a warning
MOD19: CESD (SKS)
MOD1 – MOD18
MOD6
RELAY 2
MOD1 – MOD18
MOD7
RELAY 3
MOD1 – MOD18
MOD1
RELAY 4
MOD 19
MOD19
DW-TEST
ON: Pressure switch testing is active
OFF: Pressure switch testing is not active
ON
OFF
OFF
DELAY
OPEN
ON: Gives warning before opening
OFF: Immediate opening
ON
OFF
OFF