Wall formwork
Mammut 350
Stop ends
With outside corners and
standard panels
Stop ends can also be formed
using outside corners and stand-
ard panels (Figures 40.1 to 40.3).
Panels that are 50 cm wide or
wider require additional bracing
with alignment rails (Fig. 40.3).
One alignment rail is required for
reinforcement at each tie hole
level.
For the number of assembly locks
required at the outside corner
and at the first panel joint refer
to Table 40.4.
Pouring height
Number of M assembly locks
Corner (a)
At panel joint (b)
h = 1.25 m
2
2
h = 2.50 m
2
2
h = 3.00 m
3
2
h = 3.50 m
4
3
h = 3.75 m
5
4
h = 4.25 m
6
5
h = 4.75 m
6
5
h = 5.00 m
6
5
h = 5.50 m
7
6
h = 6.00 m
8
7
h = 7.00 m
8
7
Fig. 40.2
Fig. 40.3
Table 40.4
Fig. 40.1 Height 350 cm
Description
Ref. No.
M 350 outside corner 350 ....
23-140-30
M outside corner 300 ...........
23-140-00
M outside corner 250 ............
23-140-10
M outside corner 125 ...........
23-140-20
>
50
Panel width until first
tie hole
Reinforcement with
alignment rails
required
< 50 cm
Panel width until first tie hole
Outside corners
M350-40
Technical Instruction Manual / Status November 2018