Object list - Modbus
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec
.
com
PYROCON19
Owner’s manual & Technician Settings
N°
Description
Type Value (Range)
Default
Perm. TS
1000
Temperature Outside
AV
14°F... 59°F (-10°C...+15°C)
X
R
1001
Snow Detection
BV
0..1 (1 - detected)
X
R
1002
Manual Mode
BV
0 –auto ,1 -manual
0
R/W
1003
On/Off
BV
1 – On, 0 – Off
0
R/W
1004
Time Delay Until Turn Off Heaters
AV
0…..2880 min
x
R
1005
Heater 1
BO
1 – On, 0 – Off
X
R
1006
Heater 2
BO
1 – On, 0 – Off
X
R
1007
Heater 3
BO
1 – On, 0 – Off
X
R
1008
Heater 4
BO
1 – On, 0 – Off
X
R
1009
Heater 5
BO
1 – On, 0 – Off
X
R
1010
Set Point
AV
14°F... 59°F (-10°C...+15°C)
+37°F(3.0°C) R/W P1
1011
Low Limit Heat
AV
-40°F... +32°F (-40°C...0°C)
-31°F(-35°C) R/W P2
1012
Heaters Off Delay when snow stops AV
0 … 540 min
90 min
R/W P4
1013
Manual Period Time
AV
10 … 2880 min
240 min
R/W P5
1014
Snow Sensor Sensitivity
AV
20 …80%
50%
R/W P8
1015
Snow Detection Threshold
AV
0 … 60 min
1 min
R/W P88
1016
Heater Mode
AV
Heater Mode
0
R/W P7
1017
Staggering Time
AV
1 … 600 min
120 min
R/W P6
1018
Commissioning Mode
BV
1 – On, 0 – Off
0
R/W P10
1019
C/F Scale
BV
1 - °C / 0 -°F
0
R/W
1020
Upper Limit
AV
+41°F... +113°F (+5°C...+45°C) +86°F(+30°C) R/W
1021
Upper Limit Sensor Effective
AV
+41°F... +113°F (+5°C…+45°C) X
R
1022
Upper Limit Enable
BV
0 – disable , 1 – enable
0 (disable)
R/W
1023
Ground Sensor Detection
BV
0 …1 (1 - detect)
X
R
1024
Gutter Sensor Detection
BV
0 …1 (1 - detect)
X
R
1025
3
rd
Party Sensor Detection
BV
0 …1 (1 - detect)
X
R
1026
Restore Default
BV
0…1 (1 - restore)
0
R/W
1027
Ground Fault
BV
0 – Ok, 1 – Fault
X
R
MODBUS RTU Mode, Address Slave 1-127,
Baud rate: 9600, n, 8, 1
Supported Commands:
0x03 = Read Holding Registers (for all).
0x06 = Preset Single Register (For R/W registers only),
Command 0x2B is used to identify controller
Vendor Url
= “meitavtec.com”
Product Name = “Pyrocon
19
”
User Application Name = “Pyrocon 19”
VendorName = "Meitav-Tec".
ProductCode = "19418301"
MajorMinorRevision = "0.1.2257”
The MODBUS Register No. X is addressed in the MODBUS Register Address (PDU) X-1.
All Registers are signed Integer 16 bit.
Pg. 22