Technician settings (Cont’)
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec
.
com
PYROCON19
Owner’s manual & Technician Settings
Pg. 17
P13 – Not in use
P14 – Reset PYRO Sensors MAC Address
Press the [SELECT] and [+] buttons simultaneously.
“P14” will appear on display.
Use the [+] and [-] buttons to select sensor by its MAC address.
Press the [ON] button to reset the sensor’s MAC address.
Press the [SELECT] and [+] buttons simultaneously.
“P13” will appear on display - Continue to P14
P15 – Offset for calibration of measures temperature
Press the [SELECT] and [+] buttons simultaneously.
“P15” will appear on display.
Use the [+] and [-] buttons to adjust the offset.
Range: -9…+9°F / -6…+6°C
Default: 0°F / 0°C
In order to save changes and return to normal display, move DIP switch S1
back to OFF position.
Restore default values
Important: Make sure the unit is turned OFF (the word “OFF” should appear on display).
Move DIP switch S1 to ON position.
Press and hold the [ON] button for 10 seconds. The thermostat will beep.
Move DIP switch S1 back to OFF position.
Save changes and return to normal display
Important: Changes made to technician parameters will not take effect as
long as DIP switch S1 is in ON position.