Object list - BACnet
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec
.
com
PYROCON19
Owner’s manual & Technician Settings
N°
Object
Value
Object name
Default
Perm. TS
1
AnalogValue_#0
-10...15°C (14...59°F)
SetPoint
3°C (37°F)
R/W
2
AnalogValue_#1
-40...0°C (-40...32°F)
LowLimitHeat
-35°C (-31°F) R/W
3
AnalogValue_#2
0...540 min
HeatersOffDelay
90 min
R/W
4
AnalogValue_#3
10...2880 min
ManualPeriodTime
240 min
R/W
5
AnalogValue_#4
20...80%
SnowSensorSensitivity
50 %
R/W
6
AnalogValue_#5
0...60 min
SnowDetectionThreshold
1 min
R/W
7
AnalogValue_#6
1...600 min
StaggeringTime
120 min
R/W
8
AnalogValue_#7
-40...35°C (-40...95°F) TemperatureOutside
-
R
9
AnalogValue_#8
0...2880 min
HeatersOffTimeDelay
-
R
10
AnalogValue_#9
0...4
HeaterMode
0
R/W
11
AnalogValue_#15
5...50°C (41...122°F)
UpperLimit
30°C (86°F) R/W
12
AnalogValue_#16
5...50°C (41...122°F)
UpperLimitSensorEffective
-
R
13
BinaryOutput_#0
1-On,0-Off
Heater 1
-
R
14
BinaryOutput_#1
1-On,0-Off
Heater 2
-
R
15
BinaryOutput_#2
1-On,0-Off
Heater 3
-
R
16
BinaryOutput_#3
1-On,0-Off
Heater 4
-
R
17
BinaryOutput_#4
1-On,0-Off
Heater 5
-
R
18
BinaryValue_#0
1-On,0-Off
OnOff
0-Off
R/W
19
BinaryValue_#1
1-On,0-Off
Manual Mode
0-Off
R/W
20
BinaryValue_#2
1-On,0-Off
C_F_Scale
0-Off
R/W
21
BinaryValue_#3
1-On,0-Off
SnowDetection
0-Off
R
22
BinaryValue_#4
1-On,0-Off
CommissioningMode
0-Off
R/W
23
BinaryValue_#5
1-On,0-Off
RestoreDefaults
0-Off
R/W
24
BinaryValue_#9
1-On,0-Off
GroundSensorDetection
0-Off
R
25
BinaryValue_#10
1-On,0-Off
Up
p
erLimitEnable
0-Off
R/W
26
BinaryValue_#11
1-On,0-Off
GutterSensorDetection
0-Off
R
27
BinaryValue_#12
1-On,0-Off
3rdPartySensorDetection
0-Off
R
28
BinaryValue_#14
1-On,0-Off
GroundFault
0-Off
R
BACnet MSTS
Baud rate: 9600, 19200, 38400, 76800 no parity, 8 data bits, 1stop bit
Pg. 24