PYROCON19
Owner’s manual & Technician Settings
Pg. 12
Cont’
Technician settings (Cont’)
Value
Heaters controlled by
PYROSENSE / PYROSENSE-GROUND
Heaters controlled by
PYROSENSE-GUTTER
(when connected)
3
Snow on any sensor will trigger all heaters
Heaters 1,2
by PYROSENSE
Heaters 3,4,5*
-
-
Heater 5
Heaters controlled by
3
rd
Party sensor
-
Heaters 1,2,3,4
Heaters 1,2,3,4
Heater 5
-
0
Heaters 1,2,3,4,5*
-
-
1
Heaters 1,2,3,4
Heater 5
-
-
2
-
Heaters 1,2,3,4,5
4
Heaters 1,2
by PYROSENSE
Heaters 3,4
Heater 5
-
P07 - Heaters outputs logic controlled by PYRO sensors or by 3
rd
party sensor
Press the [SELECT] and [+] buttons simultaneously.
“P07” and the figures “0”, “1”, “2” or “3” will appear on display.
Use the [+] and [-] buttons to define the heaters logic (model dependent) as follows:
The snow sensors will control heaters upon the following logic:
1 Sensor
2 Sensors
3 Sensors
4 Sensors
Heaters 1,2,3,4
Sensor 1 – Heaters 1,2
Sensor 2 – Heaters 3,4
Sensor 1 – Heater 1
Sensor 2 – Heater 2
Sensor 3 – Heaters 3,4
Sensor 1 – Heater 1
Sensor 2 – Heater 2
Sensor 3 – Heater 3
Sensor 4 – Heater 4
Note: Sensors order (1,2,3,4) is defined by their MAC address order.
example: 3 sensors connected:
1 x PYROSENSE (MAC 1 – Sensor 1)
- Will control heater 1
1 x PYROSENSE (MAC 2 – Sensor 2)
- Will control heater 2
1 x PYROSENSE-GROUND (MAC 5 – Sensor 3) - will control heaters 3,4
*Heaters 4 and 5 will turn ON and OFF together.