PYROCON19
Owner’s manual & Technician Settings
Pg. 10
Technician settings (Cont’)
P05 - Manual mode ON time
Press the [SELECT] and [+] buttons simultaneously.
“P05”, “On” and the “Manual ON” mode time period will appear on display.
The hours will blink.
The delay time parameter defines a time frame in which the heaters remain
ON after receiving an “Manual ON” command.
Use the [+] and [-] buttons to adjust the hours of the working time.
Range: 00...48 hours
Default: 6 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the working time.
Range: 00...59 minutes
Default: 00 minutes
Manual ON
hours
Manual ON
minutes
Cont’
P04 -Time delay before stopping the heaters
Press the [SELECT] and [+] buttons simultaneously.
“P04”, “dL” and the time delay before stopping the heaters (Hold ON) will
appear on display. The hours will blink.
Use the [+] and [-] buttons to adjust the hours of the time delay.
Range: 0...9 hours
Default: 1 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the time delay.
Range: 00...59 minutes
Default: 30 minutes
Note 1. The time delay countdown will start when the snow detection signal
from snow sensor controlling the specific heater will switch from
positive to negative.
Note 2. The staggering sequence will continue during the time delay period.
Note 3. The heater icon will blink when the heater is in off delay time.
Time delay
hours
Time delay
minutes